Data: Transients in Indirect Symmetrical Phase Shift Transformers

- Citation Author(s):
-
Pallav BeraCan Isik
- Submitted by:
- Pallav Bera
- Last updated:
- DOI:
- 10.21227/d8fv-6257
- Research Article Link:
- Categories:
- Keywords:
Abstract
This data-set consists of 3-phase differential currents of internal faults and 4 other transients cases for Phase Angle Regulators (PAR). The transients other than faults include magnetizing inrush, sympathetic inrush, external faults with CT saturation, and overexcitation conditions.
PSCAD/EMTDC software is used for simulation of the internal faults and the transients.
Instructions:
The files - ’fault_location_pha’, ’fault_location_phb’, and ’fault_location_phc’ have phase a,b,c differential currents for 46872 cases. Each row has 167 samples (one cycle). In fault_location_target’- the first 33480 are faults in series unit, next 13392 are faults in exciting unit. The files - ’transients_pha’, ’transients_phb’, and ’transients_phc’ have phase a,b,c differential currents for 13680 cases. Each row has 167 samples (one cycle). In fault_transient_target’- the first 720 - overexcitation, next 2520 - magnetizing inrush, next 2520 -sympathetic inrush, and next 7920 are external faults.
Please cite:
Pallav Bera, Can Isik. (2020). Data: Transients in Indirect Symmetrical Phase Shift Transformers. IEEE Dataport. https://dx.doi.org/10.21227/d8fv-6257