Anti-islanding

This dataset contains (1) the Simulink model of a three-phase photovoltaic power system with passive anti-islanding protections like over/under current (OUC), over/under voltage (OUV), over/under frequency (OUF), rate of change of frequency (ROCOF), and dc-link voltage and (2) the results in the voltage source converter and the point of common coupling of the photovoltaic system during islanding operation mode and detection times of analyzed anti-islanding methods.

Categories:
1740 Views

This work presents a novel Anti-Islanding (AI) protection of Photovoltaic (PV) Systems based on monitoring the dc-link voltage of the PV inverter. A PV System equipped with AI protection like frequency relays, a rate of change of frequency (ROCOF) relay, and respectively the proposed dc-link voltage relay is simulated under the conditions of islanding and the detection time for all these AI techniques are compared. The study shows under which conditions our proposed dc-link voltage AI relay is the most efficient.

Categories:
2524 Views

This work presents a Matlab/Simulink study on anti-islanding detection algorithms for a 100kW Grid-Connected Photovoltaic (PV) Array. The main focus is on the islanding phenomenon that occurs at the Point of Common Coupling (PCC) between Grid-Connected PV System and the rest of the electric power system (EPS) during various grid fault conditions. The Grid-Connected PV System is simulated under the conditions of islanding, and anti-islanding (AI) relay reaction times are measured through the simulation.

Categories: