20kV PILC Cable Historical Inspection Data

Citation Author(s):
Riley Alden
Submitted by:
riley alden
Last updated:
DOI:
10.21227/babt-n267
No Ratings Yet

Abstract

20kV PILC Cable Historical Inspection Data from year 2007 to 2019 from an European utility company 

Instructions:

Inspected attributes are partial discharge, TD stability, differential TD, mean TD, visual condition (5 levels) and neutral corrosion percentage. 

TD Stability is tan-delta stability. Delta TD is differential tan-delta. Mean TD is mean tan-delta. These three metrics follow IEEE 400.2-2013. Partial Discharge was measured in pC according to IEC 60270. Neutral corrosion was measured by using time domain reflectometer (TDR) during cable inspection.