The work starts with a short overview of grid requirements for photovoltaic (PV) systems and control structures of grid-connected PV power systems. Advanced control strategies for PV power systems are presented next, to enhance the integration of this technology. The aim of this work is to investigate the response of the three-phase PV systems during symmetrical and asymmetrical grid faults.

Instructions: 

1. Open the "Banu_power_PVarray_grid_EPE2014_.slx" file with Matlab R2014a 64 bit version or a newer Matlab release. 2. To simulate various grid faults on PV System see the settings of the "Fault" variant subsystem block (Banu_power_PVarray_grid_EPE2014_/20kV Utility Grid/Fault) in Model Properties (File -> Model Properties -> Model Properties -> Callbacks -> PreLoadFcn* (Model pre-load function)):           MPPT_IncCond=Simulink.Variant('MPPT_MODE==1')           MPPT_PandO=Simulink.Variant('MPPT_MODE==2')           MPPT_IncCond_IR=Simulink.Variant('MPPT_MODE==3')           MPPT_MODE=1           Without_FAULT=Simulink.Variant('FAULT_MODE==1')           Single_phases_FAULT=Simulink.Variant('FAULT_MODE==2')           Double_phases_FAULT=Simulink.Variant('FAULT_MODE==3')           Double_phases_ground_FAULT=Simulink.Variant('FAULT_MODE==4')           Three_phases_FAULT=Simulink.Variant('FAULT_MODE==5')           Three_phases_ground_FAULT=Simulink.Variant('FAULT_MODE==6')           FAULT_MODE=1 3. For more details about the Variant Subsystems see the Matlab Documentation Center: https://www.mathworks.com/help/simulink/variant-systems.html or https://www.mathworks.com/help/simulink/examples/variant-subsystems.html

Categories:
4194 Views

This dataset contains (1) the Simulink model of a three-phase photovoltaic power system with passive anti-islanding protections like over/under current (OUC), over/under voltage (OUV), over/under frequency (OUF), rate of change of frequency (ROCOF), and dc-link voltage and (2) the results in the voltage source converter and the point of common coupling of the photovoltaic system during islanding operation mode and detection times of analyzed anti-islanding methods.

Instructions: 

The anti-islanding protection relays are included in the "Relay Protection Bus B20 (20 kV)" subsystem.

Categories:
50 Views

This work presents a Matlab/Simulink study on anti-islanding detection algorithms for a 100kW Grid-Connected Photovoltaic (PV) Array. The main focus is on the islanding phenomenon that occurs at the Point of Common Coupling (PCC) between Grid-Connected PV System and the rest of the electric power system (EPS) during various grid fault conditions. The Grid-Connected PV System is simulated under the conditions of islanding, and anti-islanding (AI) relay reaction times are measured through the simulation.

Instructions: 

1. Open the "Fault3_50Hz_Banu_PVarray_Grid_IncCondReg_det_AI_2013_.slx" file with Matlab R2013b or a newer release to simulate the 100kW Grid-Connected PV Array (Detailed Model) with Anti-Islanding Relays. 2. To see the Anti-Islanding Protection Relays and its settings, open the "Relay Protection Bus B20 (20kV)" block.

Categories:
1389 Views